Micro Differential Pressure Sensor HPT-8

市 场 价: 0元/个

优 惠 价: 0元/个

4-20MA output, micro differential pressure sensor for air/gas, range-0.1~0.1MPa
Micro Differential Pressure Sensor HPT-8

Micro Differential Pressure Sensor HPT-8

     Micro Differential Pressure Sensor

I. Introduction

The differential pressure transmitter adopts high-precision, high-sensitivity gas differential pressure measuring elements, and converts the pressure

signal of the measured medium into a standard analog signal or digital signal through a stable, reliable and strong anti-interference ability amplifying

circuit. The packaging technology and perfect testing process ensure the excellent performance of the product, and it is widely used in the fields of

industrial automation such as petroleum, chemical industry, metallurgy, environmental protection, measurement, automation control engineering and production

process testing.

 

II. Parameters

Ø Test medium: gas compatible with the material       

Ø Measuring range: any interval within -0.1~0.1MPa

Ø Accuracy0.1%FS0.25%FS0.5%FS

Ø Stability±0.25%FS/年、 ±0.5%FS/year

Ø Output4~20mA0~10VRS485

Ø Work voltage12~36V DCDefault24V±5%Ripple1%

Ø Power influence: less than 0.01%/V of output range

Ø Work temperature-20~60℃    

Ø Compensate temperature-20~60

Ø Temperature influence: ±1.55%FS/year, ±3.0%FS/year

Ø Overload300%

Ø Load Resistance420mA                     

(Among them: U is the power supply voltage, RD is the internal resistance of the cable)

 


 

 

  

III. Wire definition 


Wire 

 Signal

Red

Black

Yellow

Blue

4-20mA(two wires

24V+

Signal

\

\

0-10V(three wires

24V+

24V-

Signal

\

RS485

24V+

24V-

A

B

IV. Wire connection

Ser

Symbol

Menu name

Value range

Menu remarks

1

UNIT

Unit optional

MPa;PSI;℃;mH2O

Unit indicator switch

2

dot

Decimal

0~3bit

Decimal point position switch

3

ZERO

Lower limit of measuring range

-19999~99999

Factory setting, please do not modify*

4

FULL

Upper limit of measurement range

-19999~99999

Factory setting, please do not modify*

5

OFF

Zero point correction

00.00~99.99

Zero point deviation compensation, default 0    note1

6

Adr

Address

01

Mailing address, default 01

7

bps

Baud rate

9600

Baud rate, default 9600

8

CUT

Zero cut range

0~1000(means 0~100.0%)

Default 20 (representing 2.0%)    note2

9

FLT

Digital filter time constant

0~250

Default 005         note3

10

SAUE

Save Settings

YES or NO

Select YES, press the confirm button to save the setting

11

End

Exit

 

Exit settings

Note 1: This parameter can compensate the deviation between the displayed value and the actual value. For example, the display value

 is 10.05, and the zero point correction is set to -0.05, then the display value after compensation is 10.00;

Note 2: This parameter can cut off the small signal displayed at the zero point. For example, 0 pressure is displayed as 0.05, and it

 can be reset to zero by increasing the setting value of the cutting range;

Note 3: This parameter can improve the stability of the display value, the larger the set value, the slower the display refresh

 

V. Troubleshooting

Failure phenomenon

Cause Analysis

Solution

Zero output exceeded

Accuracy error range

·Damaged diaphragm

·Gauge type product back pressure tube is not open to atmosphere

·Need to return to the factory for repair

·Low pressure products should use air-conducting cables and the air-conducting pipe should be connected to the atmosphere

The acquisition device has no display or the displayed value does not match the actual pressure

·Wiring error

·Transmitter has no signal output

·The output signal and the pressure range are calibrated incorrectly

·Check the wiring according to the wiring method corresponding to the transmitter output signal

·Measuring transmitter output signal

·Recalibrate the acquisition device according to the range and output of the transmitter label

The output signal does not match the actual pressure

·The temperature of the medium or the environment exceeds the limit

·The supply voltage exceeds the limit

·External load is too large

. Install a cooling device at the pressure inlet or move the transmitter to a low temperature environment and retest

·Adjust the power supply voltage

·Adjust the external load

Irregular output jump when pressure is constant

·Transmitter is not grounded

·Strong radio frequency interference on site

· Shielded cables are not used

·Use shielded cables and the shielding layer is grounded

·Reliable connection between transmitter and earth

 

VI. After sales service

Ø All orders of our company's products can enjoy one-year warranty;

Ø If the product fails during the warranty period, it is a quality problem detected by our company, and our company bears all maintenance costs;

Ø Failure to follow the specifications in this manual or disassembling the product without authorization has caused damage to the components or

damage to the pressure diaphragm, which is not covered by the product warranty。

Ø After the product fails, please contact our company. Please attach the following information to confirm the repair:

1. Product failure;

2. Product use site environment description;