Micro Differential Pressure Sensor
I. Introduction
The differential pressure transmitter adopts high-precision, high-sensitivity gas differential pressure measuring elements, and converts the pressure
signal of the measured medium into a standard analog signal or digital signal through a stable, reliable and strong anti-interference ability amplifying
circuit. The packaging technology and perfect testing process ensure the excellent performance of the product, and it is widely used in the fields of
industrial automation such as petroleum, chemical industry, metallurgy, environmental protection, measurement, automation control engineering and production
process testing.
II. Parameters
Ø Test medium: gas compatible with the material
Ø Measuring range: any interval within -0.1~0.1MPa
Ø Accuracy:0.1%FS、 0.25%FS、 0.5%FS
Ø Stability:±0.25%FS/年、 ±0.5%FS/year
Ø Output:4~20mA、0~10V、RS485
Ø Work voltage:12~36V DC(Default:24V±5%,Ripple<1%)
Ø Power influence: less than 0.01%/V of output range
Ø Work temperature:-20~60℃
Ø Compensate temperature:-20~60℃
Ø Temperature influence: ±1.55%FS/year, ±3.0%FS/year
Ø Overload:300%
Ø Load Resistance:4~20mA
(Among them: U is the power supply voltage, RD is the internal resistance of the cable)
III. Wire definition
Signal |
Red |
Black |
Yellow |
Blue |
4-20mA(two wires) |
24V+ |
Signal |
\ |
\ |
0-10V(three wires) |
24V+ |
24V- |
Signal |
\ |
RS485 |
24V+ |
24V- |
A |
B |
IV. Wire connection
Ser |
Symbol |
Menu name |
Value range |
Menu remarks |
1 |
UNIT |
Unit optional |
MPa;PSI;℃;mH2O; |
Unit indicator switch |
2 |
dot |
Decimal |
0~3bit |
Decimal point position switch |
3 |
ZERO |
Lower limit of measuring range |
-19999~99999 |
Factory setting, please do not modify* |
4 |
FULL |
Upper limit of measurement range |
-19999~99999 |
Factory setting, please do not modify* |
5 |
OFF |
Zero point correction |
00.00~99.99 |
Zero point deviation compensation, default 0 note1 |
6 |
Adr |
Address |
01 |
Mailing address, default 01 |
7 |
bps |
Baud rate |
9600 |
Baud rate, default 9600 |
8 |
CUT |
Zero cut range |
0~1000(means 0~100.0%) |
Default 20 (representing 2.0%) note2 |
9 |
FLT |
Digital filter time constant |
0~250 |
Default 005 note3 |
10 |
SAUE |
Save Settings |
YES or NO |
Select YES, press the confirm button to save the setting |
11 |
End |
Exit |
|
Exit settings |
Note 1: This parameter can compensate the deviation between the displayed value and the actual value. For example, the display value
is 10.05, and the zero point correction is set to -0.05, then the display value after compensation is 10.00;
Note 2: This parameter can cut off the small signal displayed at the zero point. For example, 0 pressure is displayed as 0.05, and it
can be reset to zero by increasing the setting value of the cutting range;
Note 3: This parameter can improve the stability of the display value, the larger the set value, the slower the display refresh;
V. Troubleshooting
Failure phenomenon |
Cause Analysis |
Solution |
Zero output exceeded Accuracy error range |
·Damaged diaphragm ·Gauge type product back pressure tube is not open to atmosphere |
·Need to return to the factory for repair ·Low pressure products should use air-conducting cables and the air-conducting pipe should be connected to the atmosphere |
The acquisition device has no display or the displayed value does not match the actual pressure |
·Wiring error ·Transmitter has no signal output ·The output signal and the pressure range are calibrated incorrectly |
·Check the wiring according to the wiring method corresponding to the transmitter output signal ·Measuring transmitter output signal ·Recalibrate the acquisition device according to the range and output of the transmitter label |
The output signal does not match the actual pressure |
·The temperature of the medium or the environment exceeds the limit ·The supply voltage exceeds the limit ·External load is too large |
. Install a cooling device at the pressure inlet or move the transmitter to a low temperature environment and retest ·Adjust the power supply voltage ·Adjust the external load |
Irregular output jump when pressure is constant |
·Transmitter is not grounded ·Strong radio frequency interference on site · Shielded cables are not used |
·Use shielded cables and the shielding layer is grounded ·Reliable connection between transmitter and earth |
VI. After sales service
Ø All orders of our company's products can enjoy one-year warranty;
Ø If the product fails during the warranty period, it is a quality problem detected by our company, and our company bears all maintenance costs;
Ø Failure to follow the specifications in this manual or disassembling the product without authorization has caused damage to the components or
damage to the pressure diaphragm, which is not covered by the product warranty。
Ø After the product fails, please contact our company. Please attach the following information to confirm the repair:
1. Product failure;
2. Product use site environment description;